HMI Solutions - FactoryTouch

Knowledge Base

FactoryTouch Connection & Issue Resolution

This article provides a practical reference for connecting, configuring, and troubleshooting a FactoryTouch unit. Use it during installation, first-time network setup, and common issue resolution in plant environments.

Use this guide when: a unit is being installed for the first time, the device loses connection to FactoryBrain, or an operator reports power, display, NFC, or barcode scanner issues.

Connection prerequisites

Before powering on or configuring the unit, confirm the required physical connections and supporting equipment are available.

Requirement

Details

Why it matters

Network cable

Ethernet RJ45 S/FTP Cat6 cable connected to a local network switch

Provides the wired network path required for communication with FactoryBrain

Network port

Available physical RJ45 Gigabit Ethernet port on an industrial network switch

Ensures the unit can join the plant network with appropriate bandwidth and reliability

Power supply

Input 100–230 V, 50–60 Hz, 1.4 A; output 12.0 VDC, 5.42 A using the provided USB-C power brick

Supplies the correct voltage and current for stable operation

Input device

USB keyboard required for initial network configuration

Needed to open the network configuration flow during startup

For best results, use the provided power brick and a known-good Ethernet cable connected to an active industrial switch port.

Network setup and reconfiguration

FactoryTouch supports a keyboard-based network configuration path during startup. This is especially useful during first-time setup or after a network change.

Initial setup access

  1. Reboot the unit from the GUI, or hold the power button for 5 seconds to turn the unit off.

  2. Power the unit back on.

  3. When Loading modules up... appears during startup, press [CTRL] + [ALT] + [SHIFT] + [P] simultaneously.

  4. Use the network configuration menu to review or update the IP address, netmask, and gateway settings so they match local plant network requirements.

When connection to FactoryBrain is lost

If the unit loses connection to FactoryBrain, use the same reconfiguration path to review network settings and restore connectivity.

  • Reboot the system, or hold the power button for 5 seconds to shut it down and then power it back on.

  • During startup, press [CTRL] + [ALT] + [SHIFT] + [P] when Loading modules up... appears.

  • Verify the configured IP address, netmask, and gateway.

  • Confirm the Ethernet RJ45 S/FTP Cat6 cable is securely attached to an active switch port.

A USB keyboard is required for the initial network configuration flow. If no keyboard is connected, the startup shortcut cannot be entered.

Troubleshooting matrix

Use the following issue-to-action table for common FactoryTouch symptoms.

Problem

What to check

Recommended action

Escalate when

FactoryTouch unit does not power on

AC/DC adapter connection, local AC source, rear power button condition

Confirm the power adapter is properly plugged into the unit and outlet, verify the outlet is supplying power, and inspect the rear power button for visible damage or sticking

The unit still does not power on after confirming power source and hardware condition

Display screen remains black

Power Status LED, physical cable or component damage

Check the bottom Power Status LED. If it is red or orange, the unit may be in Sleep or Hibernate mode; press the power button once to wake it. Inspect visible cables and components for cracks or damage

The display remains black after wake attempt and no obvious power issue is found

No Bootable Device Found

Operating system image on internal drive

Confirm the operating system image was properly loaded onto the internal drive and restart the system

The OS still fails to load after restart; contact Plantformance technical support

NFC reader fails to scan or unlock application

Badge type, badgeID configuration, user session state

Verify supported Plantformance NFC badges are being used, confirm the user's badgeID is configured in the Factory Configurator application, and ensure the user is already logged into the Ignition application

NFC still does not lock or unlock an active session after configuration has been verified

Barcode scanner is not scanning items

2D barcode scanner configuration in Ignition

Confirm the scanner is enabled and properly configured in the Ignition application settings

The scanner remains non-functional after configuration review

NFC behavior note: NFC is intended only for locking and unlocking an already active Ignition session. It is not used for initial login.

Safety and environmental limits

Operate and clean the unit within the following limits to reduce equipment risk and avoid preventable failures.

Category

Specification

Guidance

Operating temperature

0°C to 35°C

Keep the device within this temperature range during normal operation

Humidity

20% to 80% non-condensing

Avoid environments where condensation may form on internal or external surfaces

Screen cleaning

Do not spray cleaning solution directly onto the screen

Apply cleaner to a cloth first, then wipe the screen gently

Cleaning chemicals

Avoid alcohol and abrasive solvents

Use non-abrasive cleaning methods to protect the display surface

Best practice: Validate power, network cable connection, and switch port activity before moving to software or configuration troubleshooting. These checks resolve many installation and connectivity issues quickly.

Quick reference checklist
  • Confirm the provided USB-C power brick is connected and the power source is active

  • Check the Ethernet RJ45 S/FTP Cat6 cable and switch port status

  • Attach a USB keyboard before attempting initial network configuration

  • Use [CTRL] + [ALT] + [SHIFT] + [P] during Loading modules up... to open network setup

  • Verify IP address, netmask, and gateway match plant network requirements

  • For NFC issues, verify supported badge use and badgeID configuration

  • For barcode issues, confirm scanner settings in Ignition

Last updated: